Copper vs Aluminium cables: which is best for electrical installations?

For more information, please visit our website.

By Clyde Pellew, Principal Electrical Engineer

Humans first started using copper some 10,000 years ago. For a long time it was the only known and used metal, and after its electrical properties were discovered it was exploited as the conductor of choice for electrical applications.

However, our ever-increasing appetite for electrical products, and therefore demand for copper, has gradually increased the cost of using copper as a commodity. As a result, we&#;ve seen cheaper alternatives to copper being explored and increasingly used for electrical applications.

The leading alternative? Aluminium.

According to the International Annealed Copper Standard (IACS), although aluminium only has 61% of the conductivity of copper it is only 30% of the weight, and therefore significantly cheaper.

So, does this mean we should be choosing aluminium over copper for electrical applications?

Not necessarily &#; as there are pitfalls we need to be mindful of.

The pitfalls of using aluminium

The old adage &#;if it sounds too good to be true, it probably is&#; can be aptly applied to the copper v aluminium debate, particularly when it comes to cost and conductivity.

Is it really cheaper?

On paper, aluminium cables appear cheaper to purchase, but this doesn&#;t take into consideration the extra cost and effort involved in installing less pliable aluminium cables. This is why copper cables are still primarily used for the low voltage portion of works, except in situations where overhead cables are installed and weight is a factor.

What&#;s the difference in conductivity between copper and aluminium?

Aluminium cable requires a larger cross-sectional area to match the conductivity of the equivalent copper cable. This difference has a knock-on effect on several factors and may be restrictive in certain applications. As an indication, an aluminium cable needs a 56% larger cross-sectional area to achieve the same conductive capability as a copper cable. What are the pitfalls of substituting copper with equivalent aluminium conductor and how will these effect the anticipated savings?

  • If run underground, the size and number of conduits would need to increase to match the increased aluminium cable cross-sectional area.

  • If run above ground, the width of cable tray would need to increase to accommodate larger and additional aluminium cables.

  • Installation of aluminium cables are more difficult due to the flexibility and size.

  • Less aluminium cable can be stored on a drum and this can result in shorter cable lengths being available, potentially requiring more cable joints, increasing the risk of system failures.

    Mingda contains other products and information you need, so please check it out.

  • Copper is more thermally conductive than aluminium but when the larger cable sizes are factored in the differences become negligeable. Aluminium&#;s larger cable size will increase the amount of sag and may introduce destructive forces on joints.

  • The available sizes of smaller aluminium cables are limited, aluminium cable is only available at nominal cross-sectional areas of at least 16mm2

  • Bi-metallic lugs are required at every termination point at switchgear to prevent oxidation occurring between aluminium and copper connections.

  • The voltage drop (mV/A.m) for aluminium cables is higher than the equivalent copper cable (as indicated in the Figure below). This may require that aluminium cables sizes be increased to reduce the voltage drop to within rescribed limits thus reducing the oveall cost benefit. This is more noticeable when comparing smaller size cables, e.g. Cu 95mm² with Al 120mm², where the difference in price is minor compared to the &#;hidden costs&#; of changing to aluminium.


Figure 1: Voltage drop and cost per 100m for each cable size. The graphs were determined from the Nexans Olex Trade Price List (September ) cross referenced against the Prices on ElectricianSupplies.com.au website to ensure that the information is recent and relevant.

There are several other factors factors for the widespread use of copper cables that should also be taken into consideration:

  • The environmental conditions would need to be considered for any aluminium cable installation in a salty location where there may be a risk of oxidation.

  • Aluminium exhibits significant creep at room temperatures when applicable to contact pressures (connections) compared to a similar rate of creep from copper at 150°.

From a design perspective, it has been shown that changing from copper cables to aluminium cables can result in substantial changes to the electrical distribution system. Mathematically, these changes are caused by increases in voltage drop and conductivity. AS/NZS .1.1: outlines criteria that a cable must meet including current carrying capacity, voltage drop and short circuit temperature rise. When applied to larger installations, the effects can also impact the size of switchboards and selection of circuit breakers. Increases in the quantities and sizes of conduit and cable pits cannot be overlooked as this will have additional cost implications.

All of this can only be determined after the substitution is made in comparison with the to the original calculation, a substitution that should really be considered in conjunction with the lifecycle expectations of the installation.

It isn&#;t a like-for-like swap

When considering these potential risks and pitfalls of substituting copper for aluminium, its no surprise that copper cable continues to be the product of choice for most electrical designers. When considering the lifecycle costs, the financial advantages of aluminium cable lose their lustre compared to the technically superior copper cable.

If you&#;ve been considering using aluminium in lieu of copper on your next project and would like any advice or to discuss your options, get in touch with our Principal Electrical Engineer, Clyde Pellew.

 

Aluminum alloys | Information by Electrical Professionals ...

A complete DevOps platform

GitLab is a single application for the entire software development lifecycle. From project planning and source code management to CI/CD, monitoring, and security.

This is a self-managed instance of GitLab.

The company is the world’s best Aluminium Alloy Cable supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.

28 0

Comments

Join Us