The first 10 to 15 seconds after exposure to a hazardous product, especially a corrosive product, are critical. Delaying treatment, even for a few seconds, may contribute to a serious injury.
Contact us to discuss your requirements of Continuous Drench Equipments supplier. Our experienced sales team can help you identify the options that best suit your needs.
Emergency showers and eyewash stations provide on-the-spot decontamination. They allow workers to flush away hazardous products that can cause injury.
Incidental exposures can still occur even with good engineering controls and safety precautions. As a result, it is essential to look beyond the use of safe work procedures or personal protective equipment. Emergency showers and eyewash stations are necessary backups to minimize the effects of exposure to chemicals.
Emergency showers can also be used effectively in extinguishing clothing fires or for flushing contaminants off clothing.
Consult your local occupational health and safety agency in your jurisdiction and check relevant legislation for any requirements to install this equipment. Currently, there is no Canadian standard for the design or placement of eyewash stations or emergency showers. As a result, the American National Standards Institute (ANSI) Standard Z358.1-2014 (R2020) "Emergency Eyewash and Shower Equipment" is generally used as a guide. Always follow the manufacturer's instructions for installing the unit.
Note: since there is no Canadian standard for emergency showers and eyewash stations, the U.S. ANSI Standard Z358.1-2014 (R2020) was used in preparing this document.
The ANSI standard defines "flushing fluid" as any potable (drinking) water, preserved water, preserved buffered saline solution or other medically acceptable solutions. Local laws may apply in some cases. This document will use the term "water" to mean any of these acceptable flushing fluids unless otherwise specified.
ANSI Z358.1-2014 (R2020) does not specify how long the affected body part should be rinsed. It does specify that the equipment installed according to the standard is capable of providing flushing liquid for a minimum of 15 minutes.
The safety data sheet (SDS) for the hazardous product should provide guidance on flushing in Section 4: First Aid Measures.
It is agreed that it is very important that water flushing start immediately following skin or eye contact with a chemical.
"First Aid Guidelines" are available from the American Heart Association and the American Red Cross. They state that it "can be beneficial to rinse eyes exposed to toxic chemicals immediately and with a copious amount of tap water for at least 15 minutes or until advanced medical care arrives. If tap water is not available, normal saline or another commercially available eye irrigation solution may be reasonable."
Always:
In all cases, if irritation persists, repeat the flushing procedure. It is important to get medical attention as soon as possible after first aid has been given. A physician familiar with procedures for treating chemical exposure to the eyes and body should be consulted.
Emergency showers are designed to flush the user's head and body. They should not be used to flush the user's eyes because the high rate or pressure of water flow could damage the eyes in some instances. Eyewash stations are designed to flush the eye and face area only. There are combination units available that contain both features: a shower and an eyewash.
The need for emergency showers or eyewash stations is based on the properties of the chemicals that workers use and the tasks that they do in the workplace. A job hazard analysis and risk assessment can provide an evaluation of the potential hazards of the job and the work areas. The selection of protection -- emergency shower, eyewash or both -- should match the hazard.
In some jobs or work areas, the effect of a hazard may be limited to the worker's face and eyes. Therefore, an eyewash station may be the appropriate device for worker protection. In other situations, the worker may risk part or full body contact with a chemical. In these areas, an emergency shower may be more appropriate.
A combination unit has the ability to flush any part of the body or all of the body. It is the most protective device and should be used wherever possible. This unit is also appropriate in work areas where detailed information about the hazards is lacking or where complex, hazardous operations involve many chemicals with different properties. A combination unit is useful in situations where there are difficulties handling a worker who may not be able to follow directions because of intense pain or shock from an injury.
Note: All dimensions and measurements are taken from the American National Standards Institute (ANSI) standard Z358.1-2014 (R2020) "Emergency Eyewash and Shower Equipment." However, not all dimensions and measurements required by the ANSI standard are listed here.
The emergency shower should deliver a pattern of water with a diameter of at least 50.8 cm (20 inches) at 152.4 cm (60 inches). This diameter ensures that the water will come into contact with the entire body - not just the top of the person's head. ANSI also recommends the shower head be between 208.3 and 243.8 cm (82-96 inches) from the floor. The minimum flow should be 75.7 litres/minute (20 gallons/minute) for a minimum time of 15 minutes.
The shower should also be designed so that it can be activated in less than 1 second and it remains operational without the operator's hand on the valve (or lever, handle, etc.). This valve should not be more than 173.3 cm (69 inches) in height. If enclosures are used, ensure that there is an unobstructed area of 86.4 cm (34 inches) in diameter.
Eyewash stations should be designed to deliver fluid to both eyes simultaneously at a volume flow rate of not less than 1.5 litres/minute (0.4 gallons/minute) for 15 minutes. The combination eye and face wash stations require 11.4 litres per minute (3.0 gallons per minute). However, in either case, the flow should not be at a velocity which may injure the eyes. The unit should be between 83.8 and 134.6 cm (33 to 53 inches) from the floor and a minimum of 15.3 cm (6 inches) from the wall or nearest obstruction.
With an eye wash station, the user should be able to open their eyelids with their hands and still have their eyes in the liquid. In the case of the eye/face wash, the user should have enough room to allow the eyelids to be held open with the hands while the eyes and face are still in the stream. As with the shower, the unit should also be designed so that it can be activated in less than 1 second, and it remains operational without the operator's hand on the valve (or lever, handle, etc.) with the valve being located in an easily located place. Since the nozzles to eyewash stations typically need to be protected from airborne contaminants, the units are to be designed such that the removal of these covers should not require a separate motion by the user when the unit is activated.
Install and maintain according to the manufacturer's instructions. Similar requirements apply as with the plumbed units regarding the unit's ability to provide flushing liquid for at least 15 minutes, accessible access, and to deliver tepid flushing fluid. Inspect the units regularly to ensure the bladder is not expired. Once activated, the bladders must be replaced.
Designed to deliver flushing fluid immediately, personal wash units can be used while transporting the person to the permanent eyewash station or medical facility. These stations do not replace the requirement to have a 15-minute supply eyewash station. The expiry date of the fluid should be printed permanently on the unit and inspected regularly. These personal wash units are single-use and cannot be refilled.
Drench hoses may be used to "spot" rinse an area when a full shower is not required, to assist a person when the person is unable to stand or is unconscious, or to wash under a piece of clothing before the clothing is removed. The ANSI standard states that a drench hose may be considered an eyewash or eye/face wash if the drench hose meets the performance requirements as listed in the standard.
This name refers to equipment that shares a common plumbing fixture. Any of the fixtures such as shower, eyewash, eye/face wash or drench hose may be in this combination, but most commonly, it refers to a shower and an eye wash station. It is important that pressure and volume requirements for each piece of the unit (as described above) are in compliance with the code.
To be effective, the equipment has to be accessible. ANSI recommends that a person be able to reach the equipment in 10 seconds. In practical terms, consider that the person who needs the equipment will be injured and may not have use of their vision. ANSI notes that the average person can walk 16 to 17 metres (55 feet) in 10 seconds, but this does not account for the physical and emotional state of the person in an emergency.
As such, the "10-second" rule may be modified depending on the potential effect of the chemical. Where a highly corrosive chemical is used, an emergency shower and eyewash station may be required to be closer to the workstation. Refer to your risk assessment and check with a professional with knowledge in this area. These units should be installed in such a way that they do not become contaminated by corrosive chemicals used nearby.
The location of each emergency shower or eyewash station should be identified with a highly visible sign. The sign should be in the form of a symbol that does not require workers to have language skills to understand it. The location should be well-lit.
Other recommendations include that the emergency shower or eyewash station should:
The 2014 (R2020) ANSI standard recommends that the water should be "tepid" and defines this temperature as being between 16-38°C (60-100°F). Temperatures higher than 38°C (100°F) are harmful to the eyes and can enhance chemical interaction with the skin and eyes. Long flushing times with cold water (less than 16°C (60°F)) can cause hypothermia and may result in not rinsing or showering for the full recommended time (ANSI 2014). With thermal burns (injuries to the skin), the American Heart Association (2020) noted that thermal burns can be cooled with cool or cold potable water as soon as possible and for at least 10 minutes. (However, do not apply ice directly to the skin.) A temperature range for the water was not stated. Remember that any chemical splash should be rinsed for a minimum of 15 minutes, but rinsing time can be up to 60 minutes. The temperature of the water should be one that can be tolerated for the required length of time. Water that is too cold or too hot will inhibit workers from rinsing or showering as long as they should.
Install anti-scalding devices (temperature control valve or thermostatic tempering valve), constant flow meters, and other devices that will help maintain a constant temperature and flow rate. For cold or outdoor locations, emergency showers with heated plumbing are available. In hot climates, outdoor emergency showers should also have a tempering valve so that workers are not exposed to water that is too hot.
Work areas and operations that may require these devices include:
The following factors should also be considered as part of a hazard analysis when decisions are being made about the selection and use of emergency showers, eyewash stations or combination units:
All hazardous products need to be properly identified. A review of safety data sheets (SDSs) and labels can help to evaluate the hazard. To select the appropriate eyewash and shower equipment, you must know about the products you use and their potential risks.
More than one emergency shower or eyewash station may be required in an area where many workers use hazardous products. Evaluate how many workers are using the product, and provide more equipment where necessary to ensure each worker's protection.
The installation of an audible or visual alarm can alert other workers when the emergency shower or eyewash station is being used. An alarm is especially important if only one worker happens to be working in that area. A person may need help in getting to the eyewash if temporarily blinded. Some companies connect valves electrically to warning lights or buzzers in central areas.
Extra coveralls and foot covers should be stored near emergency showers. Contaminated clothes need to be removed from the injured person. Consider installing a privacy curtain (but remember to maintain the 'obstacle-free' diameter dimension as stated in the ANSI standard).
Changing the fluid in self-contained systems frequently and cleaning the units regularly can prevent the inadvertent use of contaminated fluid. Refer to the manufacturer's instructions for further details. Even in plumbed eyewash stations, the water may contain contaminants such as rust, scale and chemicals. Systems should be flushed and cleaned regularly.
It seems logical to neutralize exposure to acid with a base or vice versa. However, there are concerns that attempts to neutralize contamination of the skin or eyes could increase injury by causing:
It is critical that flushing an exposure begins as quickly as possible. Water is readily available in most situations. Follow the chemical manufacturer’s instructions but do not delay treatment to search for a specific solution.
More information about first aid for chemical exposures is available in the OSH Answers First Aid for Chemical Exposures.
Studies have shown that despite a general minimum of 15-minute flushing time being recommended, users usually only flush exposed body parts for five minutes or less. The reasons were always related to the extreme discomfort users experienced using cold water. In cold climates, the water temperature in indoor plumbed systems can be in the 2-7
64 0 0