DESCRIPTION Capacitance and Dissipation Factor (C&DF) Test Sets are used for evaluating the nature and quality of electrical insulation materials and systems. By measuring dissipation factor losses in electrical insulation, these units can indicate the presence of contaminants, fractures and punctures. As part of a routine maintenance program, capacitance and dissipation factor testing can aid in predicting potential failure of deteriorating insulation. The C&DF Test Sets include interference suppression circuits that assure accurate measurements even under severe interference or noise conditions such as those found in switchyards. They are the lightest test sets on the market, making them extremely easy to transport to the testing locations. Automatic balancing of dissipation factor (power factor) significantly reduces the required testing time and provides higher resolution.
Click here to get more.
APPLICATIONS The test sets are used for testing high-voltage electrical insulation systems. The purpose of the dissipation factor measurement of high-voltage insulation is to find early signs of weakness in the high-voltage insulation. Typical high-voltage equipment tested includes: highvoltage circuit breakers, transformers, cables and potheads, bushings, windings of rotating machines and protective surge arresters. Dissipation factor tests on high-voltage insulation are frequently made in manufacturing facilities, repair shops and in the field. By measuring dissipation factor of the specimen plus capacitance, undesirable conditions are found. They include conditions caused by moisture on or in the insulation; shorts or opens in windings or insulation; and conductive contaminants in insulating oil, gas or solid materials.
The Capacitance and Dissipation Factor (C&DF) Test Sets can perform the following standard tests:
Ungrounded Specimen Test (UST) This test is made when both specimen terminals can be insulated from ground. The test is often used to reduce the effect of stray capacitance losses to ground and to reduce the effect of interference pickup from nearby energized apparatus. Typical test specimens include the capacitive grading foils used in high-voltage bushings and the interwinding insulation used in high-voltage transformers.
Grounded Specimen Test (GST) This is the most frequently used test connection and involves all insulation between the high-voltage conductor and ground. Typical test specimens include transformer windings to tank and core, circuit-breaker assemblies, coils of rotating machines, etc
Dielectric dissipation factor testing, also known as tangent delta or power factor testing, is a measure of the dielectric losses in an insulation system. In the field of rotating machines, this technique is widely used as an appropriate means of assessing the quality of new and also aged stator winding insulation. The method is useful for assessing the uniform quality of manufacturing and the dielectric behavior of the insulation as a whole. For aged stator windings, the dielectric dissipation factor provides information about insulation condition. Certain deterioration processes, such as thermal aging or moisture absorption, will increase dielectric losses. Thus, trending of the dielectric loss over time may be employed as an indication of certain types of insulation problems.
The main principle is to measure the dielectric dissipation factor over a range of voltages and to derive different characteristic dielectric loss parameters as a basis for the evaluation. Typically, practitioners of dissipation factor measurements have used three basic parameters as a means to assess insulation condition.
This latter parameter is widely known as the dissipation factor tip-up and has been considered by many to be the key value providing some insight into insulation condition. The test methods are described in IEEE 286 and the old
IEC 60894. Empirical limits of these three parameters, verified in practice, may be used as a basis for evaluating the quality of stator winding insulation systems in manufacturing.
Until recently, the limits applied to dissipation factor measurements were largely based on internal standards or procedures developed by manufacturers and end users. As described on page 4, some limits for DF and DF tip-up have now been published in a new document, IEC 60034-27-3. Perhaps not surprisingly, these guidelines are viewed by some as too restrictive and by others as overly lenient.
Consequently, efforts are underway by some organizations, e.g. CIGRE Study Committee A1 (Rotating Machines), to assess, on an objective basis, for the appropriateness of the published limits in IEC 60034-27-3, for future revisions of this document. As part of the effort, this article reports on the results collected by Kinectrics Inc. (the old Ontario Hydro Research Group) of a study of dissipation factor results involving a large number of stator bars and coils.
Measurement of dissipation factor and tip-up is complicated by the presence of silicon carbide stress control coatings on coils or bars rated at 6 kV or above. At low voltage, the silicon carbide is essentially a very high resistance coating, and no current flows through it. However, when tested at rated line-to-ground or line-to-line voltage, by design, the silicon carbide coating will have a relativity low resistance. Capacitive charging currents flow through the insulation and through this stress relief coating. The charging currents flowing through the resistance of the coating produce an I2R loss in the coating. Since the loss is zero at low voltage and nonzero at operating voltage, the coating yields its own
Hengfeng are exported all over the world and different industries with quality first. Our belief is to provide our customers with more and better high value-added products. Let's create a better future together.
Additional resources:contribution to tip-up. This coating tip-up creates a noise floor. Very significant PD must be occurring in most windings for the PD loss to be seen above the silicon carbide tip-up.
When testing individual coils and bars, the tip-up contribution due to the stress relief coating can be minimized. The most common way is to “guard” out the currents due to the silicon carbide by overlapping the coatings with grounded aluminum foil, or even isolating the silicon carbide coating from the semicon coating, and grounding it separately. Details on guarding methods are provided in the relevant standards. An example of a stator bar with measuring and guard electrodes applied is illustrated in Figure 1.
Figure 1: A 13.8 kV stator coil undergoing dissipation factor testing with guard electrodes. One of the guard electrodes is circled in this photo. (Photo courtesy of Kinectrics)
Example Test Results
The results obtained from the analysis of the data are presented in Figures 2 and 3. There are a few points to note regarding these Figures.
TABLE I. Dissipation Factor Limits
(source: IEC 60034-27-3, Table 1)
Initial value of dissipation factor at 0.2UN 20 x 10-3 (2%) ΔDissipation factor per 0.2UN up to UN 5 x 10-3 (0.5%) Dissipation factor tip-up between 0.6UN and 0.2UN 5 x 10-3 (0.5%)Examination of Figures 2 and 3 reveals a number of features. These are,
This limited data implies that the absolute dissipation factor limit at 0.2UN recommended by IEC 60034-27-3 may be too conservative and that some consideration of this criterion may be advisable in any future revision of the document. In contrast, the findings from an examination of the dissipation factor tip-up values showed that a significant number of bars or coils failed to meet the limit required by the standard.
Figure 2. Dissipation factor % and tip-up %results for 26 groups of coils and bars manufactured using Process A.
Figure 3. Dissipation factor % and tip-up % results for 20 groups of coils and bars manufactured using Process B.
For more dissipation factor test setinformation, please contact us. We will provide professional answers.